|
Specializing In: HEATING AIR CONDITIONING HEATPUMPS HUMIDIFICATION
Useful Information
Sample Agreements
Covering Year Round
Residential Heating & Cooling
|
 |
Troubleshooting A Heatpump
Heating Mode
- Under certain weather conditions, the outside unit will develop ice buildup.
- When the unit defrosts this ice, it gives off water vapors which appears to be smoke.
- If excess ice builds up on the outside coil after more than 90 minutes elapse time, switch emergency heat to
“ON” (located on the thermostat).
- Call your serviceman if the condition does not clear.
- Auxiliary heat light “ON” (located on thermostat).
- Supplementary heaters are providing heat (usually when outside temperature is lover than 30 degrees).
- Thermostat has been adjusted up more than 1.5 degrees, which causes supplementary heaters to come on until thermostat
is satisfied.
- If auxiliary heat light stays on when the outside temperature is about 30 degrees, call serviceman.
- Little or no air flow at supply registers.
- Filters are dirty—replace.
- Blower motor or belt failure.
- Possible air leak from ducts.
- Return grill blocked
- Outside unit continuously running in moderate weather. (All units run continuously below the balance point, usually when outside temperature is lower than 30 degrees).
- Thermostat set too high.
- Thermostat needs adjustment.
- Low refrigerant level in unit.
- Outside unit coil blocked by snow, ice, etc.
Cooling Mode
Outside unit continuously running.
- Low refrigerant level in unit.
- Thermostat set very low or very warm weather.
- Outside coil partially blocked.
- Thermostat located near heat source, such as appliances, TV, etc.
- Dirty Filters or too many registers closed limiting air movement.
Unable to cool house and reduce humidity level.
- Condensation drain blocked.
- Low refrigerant level in unit.
- Possible compressor failure.
- A door or window open.
- Check for air leaks and excessive moisture in crawl space.
|