Setting A Humidistat
Generally the comfort range for humidification is between 25
percent and 50 percent RH. It is desirable to keep the humidity in the
living space within this range as long as condensation does not occur
on windows and walls. The point condensation occurs at, is affected by
the building structure and outdoor temperature. As the outdoor
temperature changes, the humidistat should be reset to keep the
humidity level in the building below the condensation point.
The set point scale of the humidistat is indexed directly to the
outdoor temperature for convenience. It is recommended that the
humidistat be set to the prevailing outdoor temperature. This provides
optimum humidity control for most installations.
If the
proper outdoor temperature setting is used and condensation forms on
the windows or walls, reduce the set point 5 F (3 C). Frost or
condensation should disappear from windows within 24 hours; if not,
continue reducing the set point until it does disappear.
If
the humidistat is set to the proper outdoor temperature and
condensation does not occur, the humidity level in the living space may
be increased if desired. Raise the humidistat set point in 5 F (3 C)
increments until condensation just begins to appear. Then reduce the
humidistat setting by 5F (3 C).
The hygrometer indicates the ambient humidity directly in percent RH.
It provides an accurate indication of the ambient relative humidity.
Wall Mount Humidistat
The humidity set point should be set for the prevailing outdoor
temperature. This provides optimum relative humidity control for most
installations. The humidity level may be adjusted to a particular
structure by using the above procedure.
Duct Mount Humidistat
If
the temperature at the humidistat location on the return air duct is
less than 80 F (27 C), use the procedure for all mounted humidistats
shown above.
If the air surrounding the humidistat is
greater than 80 F (27 C), the recommended setting should be reset to
compensate for the elevated ambient temperature. High surrounding
ambient temperatures will cause the humidistat to control at an
increased setting. To determine the compensated set point for surface
mounted humidistats with high ambient temperatures, use the following
procedure.
- With a bulb type thermometer, accurately determine the surrounding duct temperature at the humidistat location.
- Decrease
the recommended setting about 10 F (6 C) for each 5 F (3 C) above 80 F
(27 C) at the humidistat location. For example, the outdoor
temperature is 0 F (minus 18 C), and the temperature at the humidistat
is 90 F (35 C). The compensated set point should be minus 20 F for the
10 F above ambient temperature (minus 18 C setting minus 12 C for the 8
C above ambient temperature).
Checkout
Place
the system in operation and observe through at least one complete cycle
to make certain that all components are functioning properly.
|